Insulation single wires
H05V-K, H07V-K
Single core non-sheathed cables with thermoplastic PVC insulation
Applications

For internal wiring in electrical equipment.

Design
- Conductor: Stranded copper wires, class 5 to EN 60228
-
Insulation:
PVC Type TI2 to EN 50 363-3
Shore A: 88±3 - Insulation colors: White, grey, black, blue, brown, yellow, green, red, green/yellow.
Electrical data
-
Working voltage Uo/U:
H05V-K: 300/500 V H07V-K: 450/750 V -
Test voltage on finished cable a.c. 50 Hz:
H05V-K: 2000 V H07V-K: 2500 V - Specific insulation resistance at 20°C: > 20 МΩ.km
Operating conditions
-
Working temperature:
fixed installation: -30°C ÷ +70°C -
Flame behaviour: according to EN 60 332-1-2
CPR: Eca - According to standard: EN 50525-2-31
Conductor cross-section [mm2] | Overall diameter of cable | |
---|---|---|
Min [mm] | Max [mm] | |
H05V-K 300/500V | ||
0.50 | 2.10 | 2.50 |
0.75 | 2.20 | 2.70 |
1.00 | 2.40 | 2.80 |
H07V-K 450/750V | ||
1.50 | 2.80 | 3.34 |
2.50 | 3.40 | 4.10 |
4.00 | 3.90 | 4.80 |
6.00 | 4.40 | 5.30 |
10.00 | 5.70 | 6.80 |
16.00 | 6.70 | 8.10 |
25.00 | 8.40 | 10.20 |
35.00 | 9.70 | 11.70 |
50.00 | 11.50 | 13.90 |
70.00 | 13.20 | 16.00 |
95.00 | 15.10 | 18.20 |