30, Nikola Petkov Str.
5400 Sevlievo
Bulgaria
tel: 0675 3 28 68
fax: 0675 3 28 70
еmail: emka@nat.bg

LiY

Flexible insulation single cores with pvc insulation
Applications
LiY

For internal wiring in electrical equipment.


Design
  • Conductor: Stranded copper wires Class 5 to EN 60228 (DIN VDE 0295)
    (except 0.34 mm2: 7 x 0.25 mm)
  • Insulation: PVC Type TI2 to EN 50 363-3
    Shore A: 88±3
  • Insulation colors: White, grey, black, blue, brown, yellow, green, red or another by agreement.
Electrical data
  • Working voltage Uo/U:
    for 0.14 mm2: max 350 V
    over 0.14 mm2: max 500 V
  • Test voltage on finished cable a.c., 50 Hz:
    for 0.14 mm2: 1200 V
    over 0.14 mm2: 1500 V
  • Specific insulation resistance at 20°C: > 20 МΩ.km
Operating conditions
  • Working temperature:
    fixed installation: -40°C ÷ +80°C
    flexing: -5°C ÷ +70°C
  • Flame behaviour: according to EN 60 332-1-2
Core constructional data
Nominal cross-sectional of conductor [mm2] Thickness of insulation Core diameter [mm]
Specified value [mm] Min. value [mm]
0.14 0.23 0.18 max. 1.00
0.25 0.30 0.25 1.30 ± 0.05
0.34 0.38 0.30 1.50 ± 0.05
0.50 0.40 0.30 1.75 ± 0.05
0.75 0.40 0.30 1.95 ± 0.05
1.00 0.40 0.30 2.10 ± 0.05
1.50 0.40 0.30 2.40 ± 0.05